FST-610 SVC frequency inverter
Technical specifications
I/O Features | Input Voltage Range | 380/220V±15% |
Input Frequency Range | 47~63Hz | |
Output Voltage Range | 0~rated Input voltage | |
Output Frequency Range | 0~650Hz | |
I/O Terminals | Input Terminals | programmable DI: 7, 1 high speed pulse; programmable AI:2, VCI:-10V~10V, CCI2:0~10V or 0~20mA |
Output Terminals | Programmable open collector output 1(open collector or high speed pulse output selectable), programmable relay output 2 programmable AI:2, 0/4~20mA or 0~10V selectable | |
Communication Terminals | RS485 communication interface is optional, adopt Modbus-RTU communication mode. | |
Control Function | Control Mode | V/F control, sensorless vector control (SVC) |
Speed Adjusting Range | 1:100(SVC) | |
Overload Capacity | 150% rated current 60s, 180% rated current 10s. | |
Frequency Reference Source | Keypad, analog input, DI, serial communication, multi-step speed, simple PLC and PID. The combination of multi-modes and the switch between different modes can be realized. | |
Other Functions | l Traverse Control Function l PID Control Function l Simple PLC,Multi-Steps Speed Control Function: 16 steps speed can be set. l None-Stop when instantaneous power off. l Speed Trace Function: Smoothly start the running motor. l Automatic Voltage Regulation Functin (AVR): l Up to 23 fault protections over current, over voltage, under voltage, over temperature, phase failure, overload etc. | |
Man-machine Interface | LED Display | Can display setting frequency, output frequency, output voltage, output current etc. |
Multi-function Key-press | The QUICK/JOG key-press can be used as multi-function key-press. | |
Environmental Constraint | Temperature | -10°C~+40°C.Inverter will be derated if ambient temperature exceeds 40°C. |
Humidity | ≤90%, without condensation | |
Altitude | ≤1000M, output rated power >1000M, output power with derating | |
Impingement and Osciliation | The inverter is prohibited to drop on the floor or with suddenly impact, it also prohibited to be installed at the place where the osciliation may occur very probably. | |
Electromagnetic Radiation | The inverter is prohibited to be installed at the price where stronger electromagnetic radiation may occur very probably. | |
Store Environment | The inverter is prohibited to be stored at the place where with direct sunlight, fall of oil mist, steam and with heavy osciliation. |