- Contact Person : Mr. Wong Ocean
- Company Name : Anyhertz Technology (Shenzhen) Co., Ltd.
- Tel : 0086-0755-82874885
- Fax : 0086-0755-82871285
- Address : Guangdong,shenzhen,Floor 5, Factory building 3, Jianye Industrial Zone,Zhuzilin, Futian
- Country/Region : China
FST-500 mini SVC frequency converter
Main features
16-bit microprocessor controlled PWM outputAutomatic torque boost & slip compensationOutput frequency 0.1~400Hz8-step speed control & 7-step process controlLow-noise carrier frequency up to 15kHz2 accel./decel. times & S-curveProcess follower 0-10VDC, 4~20mACommunication interface RS-485 (Baud rate 38400)Energy saving & automatic voltage regulationAdjustable V/F curve & Simple vector controlAutomatic adjustment of accel./decel. TimesPID feedback controlSimple position function0 Speed Holding functionSleep I Revival function build-in
Specifications
Model Number FST-500 | 007 | 015 | 022 | 037 | 055 | 075 | |||||||||
Max. Applicable Motor Output (kW) | 0.75 | 1.5 | 2.2 | 3.7 | 5.5 | 7.5 | |||||||||
Max. Applicable Motor Output (HP) | 1.0 | 2.0 | 3.0 | 5.0 | 7.5 | 10 | |||||||||
Output rating rating
| Rated Output Capacity (kVA) | 2.3 | 3.1 | 3.8 | 6.2 | 9.9 | 13.7 | ||||||||
Rated Output Current (A) | 3.0 | 4.0 | 5.0 | 8.2 | 13 | 18 | |||||||||
Maximun Output Voltage (V) | 3-Phasc Proportional to input voltage | ||||||||||||||
Output Frequency (Hz) | 0.1 ~400Hz | ||||||||||||||
Carrier Frequency (kHz) | 1- | 15 | |||||||||||||
Input rating | Rated Input Current (A) | 3-Phasc | |||||||||||||
4.2 | 5.7 | 6.0 | 8.5 | 14 | 23 | ||||||||||
Rated Voltage. Frequency | 3-Phaso 380 to 480V . 50 / 60Hz | ||||||||||||||
Voltage Tolerance | ± 10%(342~528V) | ||||||||||||||
Frequency Tolerance | ± 5%(47—63Hz) | ||||||||||||||
Fan Cooled | |||||||||||||||
Weight (Kg) | 1.5 | 1.5 | 2.0 | 3.2 | 3.2 | 3.3 | |||||||||
Control characteristics | | Control System | SPWM (Sinusoidal Pulse Width Modulation)control (V/F or sensorless vector control) | |||||||||||||
Freq. Setting Resolution | 0.1Hz | ||||||||||||||
Output Frequency Resolution | 0.1Hz | ||||||||||||||
Torque Characteristics | Including the auto-torque, auto-slip compensation; starting torque can be 150% at 5.0Hz | ||||||||||||||
Overload Endurance | 150% of rated current for 1 minute | ||||||||||||||
ISkip Frequency | Three zones, settings range 0.1-400Hz | ||||||||||||||
|Accel/Decel Time | 0.1 to 600 seconds (2 independent settings for Accel/Decel Time) | ||||||||||||||
Stall Prevention LevelFrequency Setting | 20%-200%, Setting of Rated Current
| ||||||||||||||
DC Injection Braking | Operation frequency 0-60Hz, output 0-100% rated currentStart time 0-5 seconds, stop time 0-25 seconds | ||||||||||||||
Braking Torque | Approx. 20% (up to 125% possible with option braking resistor orbraking unit externally mounted) | ||||||||||||||
V/F Pattern | Adjustable V/F pattern | ||||||||||||||
Operating characteristics | FrequencySetting | Keypad | Set by®® | ||||||||||||
ExternalSignal | Potcntiometcr-5KQ/0.5W, 0 to +10VDC; 4 to 20mA, RS-485 interface;Multi-Function Inputs 0 to 5 (7 steps. Jog, up/down) | ||||||||||||||
Operation Setting Signal | Keypad | Set by RUN, STOP | |||||||||||||
ExternalSignal | 2 wires / 3 wires (Run, Stop, Forward / Rev, ), JOG operation,RS-485 serialinterface (MODBUS) | ||||||||||||||
Multi-Function Input Signal | Multi-step selection 0 to 7, Jog. accel/decel inhibit, first to forth accel/decel switches, counter,PLC operation, external Base Block (NC, NO), auxiliary motor control is invalid, ACI/AVIselections, drive reset. UP/DOWN key settings, sink/source selection | ||||||||||||||
Multi-Function Output Indication | AC Drive Operating, Frequency Attained, Non-zero, Base Block, Fault Indication,Local/Remote indication. PLC Operation indication. Auxiliary Motor Output, Driver is Ready,Overheat, Alarm, Emergency Stop | ||||||||||||||
| Analog Output Signal | Analog frequency/current signal output. | ||||||||||||||
Alam Output Contaact | 1Form C contact or open collector output. | ||||||||||||||
Operation Functions | AVR. S-Curve. Over-Voltage. Over-Current Stall Prevention, Fault Records. Adjustable CarrierFrequency, DC Braking, Momentary Power Loss restart, Auto Tuning, Frequency Limits,Parameter Lock/Reset, Vector Control, Counter. PID Control, PLC,MODBUS Communication, Reverse Inhibition, abnormal reset,abnomal re-start, digital frequency output, sleep/revival function,1 st/2nd frequency source selections | ||||||||||||||
Protective Functions | Self-testing, Over Voltage, Over Current, Under Voltage, Overload, Overheating, ExternalFault, Electronic thermal, Ground Fault. | ||||||||||||||
Display Keypads | 6-key. 4-digit. 7-segment LED. 4 status LEDs, master frequency, output frequency.Output current, custom units, parameter values for setup, review and faults,RUN, STOP, RESET, FWD/REV | ||||||||||||||
Environment conditions
| Protection Level | IP20 | |||||||||||||
Pollution Degree | 2 | ||||||||||||||
Installation Location | Altitude 1,000m or less, keep from corrosive gas. liquid and dust | ||||||||||||||
Ambient Temperature | -10°C to 40°C (-10°C to 50°C without blind plate) Non-Condensing and not frozen | ||||||||||||||
Storage / TransportationTemperature | -20°C to 60°C | ||||||||||||||
Ambient Humidity | Below 90% RH (non-condensing ) | ||||||||||||||
Vibration | 9.80665™^ (1G) less than 20Hz. 5.88m/s2 (0.6G) at 20 to 50Hz | ||||||||||||||
Approvals | C € © |
FST-500 mini SVC frequency converter